8 Operation
Maschinenfabrik Reinhausen GmbH 2023 614001150/12 EN MSENSE
®
DGA 2/3
Left-hand side Right-hand side
H
2
O
Water content (humidity) in %RH
1)
Oil
Oil temperature in °C
1)
The water content (humidity) display can be converted from %RH to ppm
via the MESSKO®MSET parameterization software if required (service
code 4 and 5). When the measured data is transmitted (e.g. to a SCADA
control center or a laptop), the water content is always transmitted in both
display formats.
If an asterisk (*) is displayed, the system is outside the specified measuring
range in accordance with the chapter "Technical data" [►Section 13, Page
90]. The following applies to the displayed measured value:
▪ During the first measurement after the running-in phase, the value of the
lower detection limit is displayed.
▪ If measured values within the specified measuring range have already
been recorded, then the last valid measured value is displayed.
The asterisk (*) disappears automatically as soon as the system is back in
the valid measuring range.
The default settings for the warning and alarm limits are in accordance with
the directives of IEEEC57.104 (for H2 and CO) and DINEN60422 (for wa-
ter content in oil).
You can adjust the limit values to your requirements via the
MESSKO®MSET parameterization software.
The gas formation rates can be set as both positive and negative values.
The configurable parameters per sensor value are:
▪ Concentration too high warning
▪ Concentration too high alarm
▪ Formation rate too high warning
▪ Formation rate too high alarm
Any alarms, warnings or other messages present are only shown in the dis-
play for as long as the set threshold value is exceeded.
H
2
CO H
2
O
[ppm] [ppm] [%RH] [ppm]
2)
Warning 500ppm 350ppm 30% RH 20ppm
Alarm 700ppm 570ppm 45% RH 30ppm
Gas formation rate warning 30ppm/d 30ppm/d 10% RH 10ppm/d
Gas formation rate alarm 50ppm/d 50ppm/d 15% RH 15ppm/d
2)
For mineral-based insulating oils