8 Operation
Maschinenfabrik Reinhausen GmbH 2023 634001150/12 EN MSENSE
®
DGA 2/3
The following table lists the possible events and the respective recom-
mended actions:
Event Text display Recommended action
CO concentration warning
(DGA 3 only)
CO Warn. 1
CO concentration alarm
(DGA 3 only)
CO Alarm 2
CO gas formation rate warning
(DGA 3 only)
CO Formation Warn. 1
CO gas formation rate alarm
(DGA 3 only)
CO Formation Alarm 2
H2 concentration warning H2 Warn. 1
H2 concentration alarm H2 Alarm 2
H2 gas formation rate warning H2 Formation Warn. 1
H2 gas formation rate alarm H2 Formation Alarm 2
H2O concentration warning H2O Warn. 1
H2O concentration alarm H2O Alarm 2
H2O gas formation rate warn-
ing
H2O Formation Warn. 1
H2O gas formation rate alarm H2O Formation Alarm 1
These events are saved in the database on the device and can be loaded
onto the PC with the MESSKO®MSET parameterization software. If the de-
vice has a display you can read the text display directly.
In addition, the events can be issued via the relay contacts S1...S4 and via
the communication interface.
No. Recommended action
1 Please monitor your system and have an oil sample [Section 10.3, Page
69] analyzed in a laboratory (at least DGA and humidity determination) in
good time.
Further procedures in accordance with the action instructions derived from
the laboratory results.
2 Please monitor your system and have an oil sample [Section 10.3, Page
69] analyzed in a laboratory (at least DGA and humidity determination) in
good time.
Reduce the system load until the action instructions derived from the labora-
tory results are available.