11 Removal
Maschinenfabrik Reinhausen GmbH 202382 4001150/12 ENMSENSE
®
DGA 2/3
2. Release the ball valve clamp connection.
Figure60: Releasing the ball valve clamp connection
3. Pull the device as far as possible out of the ball valve.
The chain should now be tightly tensioned.
NOTICE
Danger of damaging the measuring pipe!
If the device is operated in front of a slide valve, the tightly tensioned chain
ensures that the measuring pipe of the device has been pulled out far
enough and that the slide valve does not collide with it when closing.
Figure61: Pulling the device out