11 Removal
Maschinenfabrik Reinhausen GmbH 202384 4001150/12 ENMSENSE
®
DGA 2/3
6. Unscrew the fixing screw for the safety chain on the device far enough to
free the chain. Pull the safety chain out and screw the fixing screw back
into place.
Figure63: Releasing the link chain
7. Carefully pull the device out of the ball valve.
NOTICE
Type and source of danger
Ensure that the device does not become jammed during this procedure.
Support the weight by hand. Collect the excess oil in the collecting tray.
Figure64: Pulling the device out of the ball valve