Section 40 00-02-0716
2013-06-03 - 26 -
S-Number
Description
S81
UNIT SYSTEM: Enter either Metric or English for displayed values. Factory set to
English.
S82
TIER RATING: Enter either Tier3 or Tier4 for electronic engines. Factory set to Tier3.
S83
TIER4 STATE: Select the Regen option that best suits the application. The options to
choose are AUTO DPF REGEN or INHIBIT DPF REGEN.
Factory set to INHIBIT DPF
REGEN.
NOTE: This option only available if TIER RATING (S82) is set to
Tier4.
S84
REQUEST DPF REGEN: Selecting YES will initiate a regen. After pushing the “yes”
button, the display will go from “no” to “yes” when the regen is complete
. Allow the
controller to return to “no” before exiting the S number. The controller will remain at this S
number until the regen is complete. Factory set to NO.
NOTE: This display is only available if S82”TIER 4 RATING” is set
to 4, S38 “ENGINE TYPE” is set to ECU, the engine RPM is above
S23 “CRANK STOP RPM”, and the ECU output (Output 1) is on.
S85
AUX 1 TYPE CONFIG: Enter N.C or N.O. for auxiliary switch 1. Factory set to N.O.
S86
AUX 2 TYPE CONFIG: Enter N.C or N.O. for auxiliary switch 2. Factory set to N.O.
S87
AUX 3 TYPE CONFIG: Enter N.C or N.O. for auxiliary switch 3. Factory set to N.O.
S88
AUX 1 DELAY: Auxiliary 1 switch must remain active throughout this delay for auxiliary 1
output to turn ON
. The delay will reset if the input is removed before the delay expires.
(Adjustable from 1 to 9,999 seconds) Factory set to 1.
S89
AUX 2 DELAY: The Auxiliary 2 switch must remain active throughout this delay for
Auxiliary 2 output to turn ON. The delay will reset if the input is removed before the delay
expires. (Adjustable from 1 to 9,999 seconds) Factory set to 1.
S90
AUX 3 DELAY: The Auxiliary 3 switch must remain active throughout this delay for
Auxiliary 3 output to turn ON. The delay will reset if the input is removed before the delay
expires. (Adjustable from 1 to 999,999 seconds) Factory set to 1.
S91
S80 FUEL METRIC CONFIG. Enter “Liter/hr.” or “Imperial Gallon/hr. Factory set to
Liter/hr.
S92
S80 OIL PSI METRIC CONFIG. Enter “KPA” or “BAR Factory set to KPA.
S93
STOP FLOW: When “flow” is selected in S37, an auto stop will occur when the flow
drops to this set point. (adjustable from -500 to 10,000 GPM) Factory set to 1000 GPM.
S94
MAINTAIN FLOW: When “flow” is selected in S37, the engine will be throttled between
the “minimum” and “maximum” rpm set points to maintain this flow. (adjustable from -500
to 10,000 GPM) Factory set to 5000 GPM.