Section 40 00-02-0716
2013-06-03 - 30 -
P-Number
Description
P38
CLCK K RUN TM: This set-point lets you set in the amount of time you would like your
engine to run on your first start time. You have 12 available start times per day (A L).
Factory set to 0.0.
P39
CLCK K HR: This set-point lets you set the clock hour you would like to start in 24hr
format. For example, if you want to start in the 3 o'clock in the afternoon hour, set it to
15. Factory set to 00.
P40
CLCK K MIN: This set-point lets you set the clock minute you would like to start. For
example, if you want to start at 8:30 in the morning, you would adjust this until it read
30 in the minute portion Factory set to 00.
P41
CLCK L RUN TM: This set-point lets you set in the amount of time you would like your
engine to run on your first start time. You have 12 available start times per day (A L).
Factory set to 0.0.
P42
CLCK L HR: This set-point lets you set the clock hour you would like to start in 24hr
format. For example, if you want to start in the 3 o'clock in the afternoon hour, set it to
15. Factory set to 00.
P43
CLCK L MIN: This set-point lets you set the clock minute you would like to start. For
example, if you want to start at 8:30 in the morning, you would adjust this until it read
30 in the minute portion Factory set to 00.
P44
DISCH PSI @ SD: Shows what the discharge pressure was when the controller
initiated the last failure shutdown.
P45
LEVEL @ SD: Shows what the system level was when the controller initiated the last
failure shutdown.
P46
AMB TEMP @ SD: Shows what the ambient temperature was when the controller
initiated the last failure shutdown.
P47
OIL PSI @ SD: Shows what the engine oil pressure was when the controller initiated
the last failure shutdown.
P48
ENG TEMP @ SD: Shows what the engine jacket water temperature was when the
controller initiated the last failure shutdown.
P49
FUEL LVL @ SD: Shows what the engine fuel level was when the controller initiated
the last failure shutdown.
P50
RPM @ SD: Shows what the engine speed was when the controller initiated the last
failure shutdown.
P51
LAST SHUTDOWN: Shows what caused the last failure shutdown and the time in
running hours that it occurred.
P52-60:
##th SHUTDWN: P52 to P60 store the 2nd through the 10th cause of failure shutdown
with the date and time the shutdown occurred.
P61
RUN COUNTDOWN: This timer operates when LOCAL PUSHBUTTON is selected in
S35. Zero disables this feature. (Adjustable from 0 to 9,999 minutes) Factory set to 0.
P62
PROGRAM #: The value in this window is the program and version number. This is
helpful information to have before calling the factory for technical help.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Murphy EMS PRO and is the answer not in the manual?

Murphy EMS PRO Specifications

General IconGeneral
BrandMurphy
ModelEMS PRO
CategoryController
LanguageEnglish

Related product manuals