TYPE DESCRIPTION
Overspeed: (1) yes, (0) no.
Overcrank: (1) yes, (0) no.
High Discharge Pressure: (1) yes, (0) no.
Low Discharge Pressure: (1) yes, (0) no.
High System Level: (1) yes, (0) no.
Low System Level: (1) yes, (0) no.
Loss of Pressure Sender: (1) yes, (0) no.
Loss of Temperature Sender: (1) yes, (0) no.
Pump High Oil Temperature: (1) yes, (0) no.
(MSB) Pump Low Oil Level: (1) yes, (0) no.
Shutdown Status: The following is a description of the bits:
(LSB) Pump High Housing Temperature: (1) yes, (0) no.
Low Fuel Level Alarm: (1) yes, (0) no.
Low Fuel Level Shutdown: (1) yes, (0) no.
Discharge Pressure. Current discharge pressure.
System Level. Current system level.
Engine Start / Stop. (1) yes, (0) no. Toggle type
40014
Ambient temperature. Current ambient temperature measured by
Model 12.
through
Start Pressure. Factory set to 40 psi.
Stop Pressure. Factory set to 60 psi.
Maintain Pressure. Factory set to 50 psi.
Start Level. Factory set to 15.0 feet.