Section 40 00-02-0716
2013-06-03 - 37 -
REGISTER
#
TYPE DESCRIPTION
Bit 6
Overspeed: (1) yes, (0) no.
Bit 7
Overcrank: (1) yes, (0) no.
Bit 8
High Discharge Pressure: (1) yes, (0) no.
Bit 9
Low Discharge Pressure: (1) yes, (0) no.
Bit 10
High System Level: (1) yes, (0) no.
Bit 11
Low System Level: (1) yes, (0) no.
Bit 12
Loss of Pressure Sender: (1) yes, (0) no.
Bit 13
Loss of Temperature Sender: (1) yes, (0) no.
Bit 14
Pump High Oil Temperature: (1) yes, (0) no.
Bit 15
(MSB) Pump Low Oil Level: (1) yes, (0) no.
40009
Read Only
Shutdown Status: The following is a description of the bits:
Bit 0
(LSB) Pump High Housing Temperature: (1) yes, (0) no.
Bit 1
Low Fuel Level Alarm: (1) yes, (0) no.
Bit 2
Low Fuel Level Shutdown: (1) yes, (0) no.
Bit 3
Spare.
Bit 4
Spare.
Bit 5
Spare.
Bit 6
Spare.
Bit 7
Spare.
Bit 8
Spare.
Bit 9
Spare.
Bit 10
Spare.
Bit 11
Spare.
Bit 12
Spare.
Bit 13
Spare.
Bit 14
Spare.
Bit 15
(MSB) Spare.
40010
Read Only
Discharge Pressure. Current discharge pressure.
40011
Read Only
System Level. Current system level.
40012
Read / Write
Engine Start / Stop. (1) yes, (0) no. Toggle type
40013
Read / Write
Maximum RPM Set Point.
40014
Read Only
Ambient temperature. Current ambient temperature measured by
Model 12.
40015
through
40037
Read Only
Reserved
40038
Read / Write
Start Pressure. Factory set to 40 psi.
40039
Read / Write
Stop Pressure. Factory set to 60 psi.
40040
Read / Write
Maintain Pressure. Factory set to 50 psi.
40041
Read / Write
Start Level. Factory set to 15.0 feet.