FlexPAK 800/1000
29
EN
4.2.25 CoolTmp
Menu for seng CoolTmp. See secon ‘4.2.5 CoolTmr’.
The default sengs for CoolTmp:
ESC OK
CoolTmp 1/1
On = 97
Off = 96
On=97: The default temperature limit that is set to open Cleaning Valve
V1 “SCV”. The default seng is 97°C (207ºF).
O= 96: This parameter is set to (CoolTmp On -1), The default seng is
96°C (205ºF). Always set O to On minus 1°C (On = 97-1 = 96).
Ax=00:00: The current temperature of air exing the system.
4.2.26 TVFD-Al-Tmr
Menu for seng the maximum closing and opening mes both the upper and lower TVFD
slides. If the upper or lower TVFD slides do not close or open within the set me, an alarm
is acvated. This message is only used when TVFD advanced is acvated.
See secons:
• ‘3.3.9 TVFD Alarm! Upper Slide Not Closed’
• ‘3.3.10 TVFD Alarm! Upper Slide Not Open’
• ‘3.3.11 TVFD Alarm! Lower Slide Not Closed’
• ‘3.3.12 TVFD Alarm! Lower Slide Not Open’
ESC OK
TVFD-Al-Tmr
1/1
T = 15:00s
Ta = 00:00s
T=15:00s: Maximum me for the upper and lower TVFD slides to close
or open . The default seng is 15 seconds.
Ta=00:00: The elapsed me since the closing or open cycle began.
4.2.27 BRSTmr
Menu for seng the maximum amount of me the Bag Replacement Switch (SC2) can be
acvated. When this mer has elapsed, the unit turns o and goes into O mode and an
alarm message is displayed in the PLC. See Secon ‘3.3.7 Bag Replacement Switch Time
Out’.
ESC OK
BRSTmr 1/1
T = 30:00m
Ta = 00:00m
T=30:00: The maximum amount of me set for SC2 to be acvated. The
default seng is for 30 minutes.