FlexPAK 800/1000EN
32
4.2.35 FCDelay
FCDesay is used in ATEX applicaons.
This funcon is used to prevent the safety damper, Duct Isolaon Damper, from
unintenonally opening during lter cleaning.
During lter cleaning, high velocity air ows out of the lter housing through the safety
damper Duct Insulaon Damper, which may cause it to close.
To counteract this feature, FCDelay is acvated to close the Duct Isolaon Damper in order
to isolate the pipe system before lter cleaning and minimize the risk that it accidentally
closes.
For more informaon, see ‘8.2 Tuning Duct Isolaon Damper sequence’.
ESC OK
FCDely 1/1
TH = 01:00s
TL = 02:00s
Ta = 00:00s
TH = 1s Default seng (Do not change this parameter value!)
TL = 2s Default seng
Ta = Elapsed me since Filter Cleaning Start Impulse was acvated
4.2.36 IsoVDly
IsoVDly (T) is used in ATEX applicaons.
IsoVDly (T) is a delay mer to ensure that the Duct Isolaon Damper is closed unl vacuum
in the lter housing is higher than the duct system.
For more informaon, see ‘8.2 Tuning Duct Isolaon Damper sequence’.
ESC OK
IsoVDly 1/1
T = 04:00s
Ta = 00:00s
T = 4s: Delay, aer last FC pulse occur, before Duct Isolaon Damper
open. “Equalizaon Time”. 04:00s Default seng.
Ta = 00:00s: Elapsed me since delay started
4.2.37 DuctIsoDamp
DuctIsoDamp is used in ATEX applicaons. This funcon enables the Duct Isolaon Damper
sequence funcon.
DuctIsoDamp is used to ensure that the safety damper, Duct Insulaon Damper Safety
Damper, does not deliberately close during lter cleaning.
When enabled, sengs must be made by the Parameters (IsoVDly and FCDely).
For more informaon, see ‘8.2 Tuning Duct Isolaon Damper sequence’.
ESC OK
DuctIsoDamp 1/1
Switch = Off
Switch = O Default seng