4.2.42 Clean cycle
The me duraon for a cleaning cycle.
ESC OK
CleanCycle 1/1
Tch = 03:00s
Tpu = 02:00s
On = 1
Cnt = 0
Tch: Vacuum building me (Charge me). Default is 3 seconds.
Tpu: Clean pulse me. Default is 2 seconds.
On: Number of cleaning pulses. Default is 1 pulse. Note! Minimum
value = 1.
Cnt = 0. Elapsed cleaning cycles.
Note! If On is set to 0, no lter cleaning is performed.
5 Automac bin emptying funcon
5.1 AEB-Flap Valve sengs
5.1.1 Hardware
• The AEB-Flap Valve controlled by the V11 TVFD (SLV) Solenoid Lower Valve.
• The duct isolaon valve controlled by the V12 TVFD (SUV) Solenoid Upper Valve.
5.1.2 PLC Sengs
1. Presep Switch = O (standard seng).
2. AEB-TVFD Switch = On (standard seng).
3. TVFDAdv Switch = O (standard seng).
NOTE! Presep overrides 2 above.
NOTE! If TVFDAdv is acvated (Switch = On), TVFDAdv overrides 1 and 2 above.
5.1.3 Timer Sengs
BinOpnTm
TL = Delay me to let the motor decrease speed and the TVFD Solenoid Upper Valve to
close a duct isolaon valve before bin emptying starts. The default is 5 seconds.
TH = Emptying Time. The default is 5 seconds.
PresepTm
TL = Delay to let the bin lid to close before the motor increases speed and the TVFD
Solenoid Upper Valve to open a duct isolaon valve. The default is 5 seconds.
TH = Time delay to the next possible emptying sequence. The default is 5 seconds.
5.2 Simple TVFD Valve Sengs
5.2.1 Hardware
Simple TVFD Valve controlled by the V11 TVFD (SLV) Solenoid Lower Valve and the V12
TVFD (SUV) Solenoid Upper Valve.
5.2.2 PLC Sengs
1. Presep (Sokey) = O (standard seng).
2. AEB-TVFD (Sokey) =O (standard seng=On).
3. TVFDAdv (Sokey) = O (standard seng).