19
Ness Guardpost Installation & Programming
PROGRAMMING OPTIONS
RANGE ONBOARD PIR RANGE
Sub-menu
LOW Low range 8m (DEFAULT)
HIGH High range 14m
The onboard PIR can be walk-tested while this menu item is displayed.
PULSE ONBOARD PIR PULSE COUNT
Sub-menu
1 PULS 1 pulse count (DEFAULT)
2 PULS 2 pulse count
3 PULS 3 pulse count
4 PULS 4 pulse count
The onboard PIR can be walk-tested while this menu item is displayed.
SIGNAL RADIO SIGNAL STRENGTH CHECK
Check the signal strength
of your radio keys and radio
devices.
Note: OK light indicates
onboard PIR trigger.
Sub-menu
SEND DEVICE Waiting for device message
SENS 2-23 / LEVL 1-9 Detector received at signal strength level shown
KEY 1-23 / LEVL 1-9 Key received at signal strength level shown
Guardpost registers the rst device received and displays the signal strength (1-9), and beeps a
corresponding number of times.
• Press ON to activate Signal Check
• For a key, press PANIC; for a detector, activate the detector
• Listen to beeps, view display
• Press OFF to exit Signal Check
• Press ON to re-activate Signal Check
RADJAM RADIO JAMMING ALARM
Sub-menu
ON Enabled
OFF Disabled (DEFAULT)
SILENT Dialler report only (no local siren, display or logging). Limit of 10 reports; limit cleared on
arming. Use for transparent monitoring of radio interference.
When RADJAM is enabled Guardpost will generate a chime in modes DISARMED, HOME, HOME 2 if
it receives a continuous source of Radio Frequency Interference (RFI). In ARMED mode the system will
go into a full alarm mode.
RADSUB RADIO MESSAGE SUBSTITUTION ALARM
Sub-menu
ON Enabled
OFF Disabled (DEFAULT)
When RADSUB is enabled Guardpost will generate a CHIME alarm in DISARMED or HOME or HOME
2 modes, and a full alarm in ARMED modes if it senses an intentional radio message substitution.
SUPVIS RADIO SUPERVISION INTERVAL
Sub-menu
OFF Disabled (DEFAULT)
1 HR
4 HRS
8 HRS
16 HRS
24 HRS
If enabled, a system alarm will occur if a valid supervisory message has not been received from
supervised radio within the programmed interval.