Doc. Name: NMC-PRO
Installation Manual Revision: 2 Page: 35
Crop Management Technologies
Fan & Pad (Menu 8.2.5)
# Parameter Explanation Unit/Range Default
1.
Fan Capacity Total power of fan in kilowatts kW 9.0
2.
Pad Pump
Capacity
Total power of pad pump in kilowatts kW 7.5
3.
Minimum Out
Temperature for
Humidity
Release
Set the minimum outside air temperature to
enable humidity release
0 – 100° C 0
4.
Air Inlet release
Option to allow the Fan&Pad inlet to
operate
Yes/No Yes
5.
Air Inlet Run
time open
Time it takes for the Fan&Pad inlet to open mm:ss 00:00
6.
Air Inlet Run
time close
Time it takes for the Fan&Pad inlet to close mm:ss 00:00
7.
Air Inlet Run
time delay
Time that the Fan&Pad inlet waits before
opening/closing
mm:ss 00:00
8.
Air Inlet Extra
run time
The added time that the Fan&Pad inlet runs
to ensure that it is completely open/closed
mm:ss 00:00
9.
Minimum Air
Inlet Position for
F&P
Define the minimum position of the air inlet
to enable beginning the Fan&Pad operation
0 – 100% 10%
2. Pad Pump capacity kW
3. Min out temp for hum rel.
4. Air inlet release
5. Run time open mm:ss
6. Run time close mm:ss
7. Run time delay mm:ss
8. Extra run time mm:ss
9. Min inlet Pos for F&P %
10. Max air inlet w/rain %
11. Air inlet w/storm %
12. Air inlet when frost %
13. Air inlet Curve MV/Pos %
1.0
17.0
Yes
02:00
02:00
00:00
00:05
10
11
8
14