NMC-PRO
INSTALLATION GUIDE
Doc. Name: NMC-PRO
׀
Installation Manual Revision: 2 Page: 33
Crop Management Technologies
Misting (Menu 8.2.4)
# Parameter Explanation Unit/Range Default
1.
Misting Pump
There may be up to 4 pumps, the
technician selects the pump for Zone
“X”
NOTE: It is possible for more than one
zone to use the same pump
Pump 1 – 4
Remote
No Pump
Pump 1
2.
Pump Pre-run time
The time that the pump starts before
opening the misting valves in the zone
mm:ss 00:15
3.
Pump Post-run time
The time that the pump continues after
the last misting valve is closed
mm:ss 03:00
4.
Maximum Misting
valves together
The maximum number of misting valves
allowed at the same time (per zone)
1 – 8 2
5.
7.
9.
P Factor for Temp,
Humidity, and
VPD
P & I factors are used for the P.I.
correction process. (P) and (I)
are the
aggressiveness of the adjustment of
spray and pause time.
The calculation is explained
after this
table*
1 100% 75
6.
8.
10.
I Factor for Temp,
Humidity, and
VPD
1 100% 25
11.
Misting pump
capacity
Misting pump capacity in kilowatts 2.5
12.
Remote Pump
number
In cases where the misting pump
(parameter 1) is defined as REMOTE,
define in this parameter which pump
number it corresponds to
Pump 1 – 4 - - -
8.2.4. Misting cfg Zone 1 19/01/09 16:21
1.
Mist Pump
2. Pump Pre run time mm:ss
3. Pump Post run time mm:ss
4. Max mist valve together
5. Temp P factor %
6. Temp I factor %
7. Humidity P factor %
8. Humidity I factor %
9. VPD P factor %
10. VPD I factor %
11. Misting Pump capacity KW
12. Remote Pump number
Pump 1
00:15
03:00
2
75
25
75
25
75
25
2.5
---