Doc. Name: NMC-PRO
Installation Manual Revision: 2 Page: 31
Crop Management Technologies
Heating (Menu 8.2.3)
Parameter Explanation Unit/Range Default
1.
Network
number
NETWORKS AVAILABLE
• Four heating networks available per zone
(4-networks x 4-zones)
• One optional Floating Network available
per Zone (defined on a single zone only)
• One ON/OFF heating system per zone
Network 1-4
Floating
Network
ON/OFF
none
ON/OFF heating – Configuration 2-3
2.
Capacity for
On/Off heat
The electrical capacity of the On/Off heating
system
0-50000kW ---
For each Water Network heating – Configuration 3-12
3.
Network Flow
rate
The rate of the water flow in the heating
network in m
3
per hour
1-100 m
3
/h 1 m
3
/h
4.
P factor
P factor for the heating network, used to
reach the desired temperature through
proportional
error between the measured
air temperature and
temperature
0-10 7
5.
I factor
I factor for the heating network,
reach the desired temperature
0-10 3
6.
Pump flow
capacity
The water
flow capacity of the circulation
pump
0-9999 m
3
/h
7.
HS Pump
Electrical Power
The pump high Speed / Low speed electric
power
0-9999 kW 0
8.
LS Pump
Electrical Power
1. Network # 1 2
2. Capacity On/Off kW
3. Netw. Flow rate m3/h
4. P factor
5. I factor
6. Pump flow capac. m3/h
7. HS pump power kW
8. LS pump power kw
----
1
250.0
10
0
0
0
----
1
250.0
10
0
0
0