Model H1301 Recovery and Recycling System
Installation, Operation and Maintenance Manual
Revision-L September, 2019
Page 18 of 105
IV. System Installation (continued)
F. Receiver Storage Container Connections (continued)
Outlet Leak Testing and Evacuation Method (continued)
9. Operate the vacuum pump to achieve a minimum 2500 micron vacuum level indication
on the vacuum gauge.
10. Close the Outlet Evacuation Valve.
11. Discontinue vacuum pump operation.
12. Disconnect the vacuum pump and vacuum gauge from the Outlet Evacuation Valve.
13. Cap the Outlet Evacuation Valve.
14. Open the vapor valve of the storage container if it is closed.
The Receiving Storage Container is now ready for use.