Model H1301 Recovery and Recycling System
Installation, Operation and Maintenance Manual
Revision-L September, 2019
Page 96 of 105
VIII. Trouble Shooting Guide (continued)
B. Machine Will Not Operate
1. Machine is not connected to the main electrical power. Connect to main power per
section-IV.C.
2. Power Switch is in the off position. Place the power switch into the on position so that
the power lamp is illuminated.
3. Supply circuit breakers of the machine have been tripped. Open the lower door of the
machine and reset the tripped breakers. Consult the factory if the breakers continue to
trip.
4. User power supply is not the one as directed by this manual. Consult the factory.
C. Cooling System will Not Operate
1. Cooling System Temperature Controller Power Switch is in the OFF position. Place the
power switch to the ON position.
2. Cooling Controller requires maintenance Refer to section- VII.P: Cooling Controller
Setting.
3. Refer to the enclosed PP Series Temperature Chamber Manual for further
troubleshooting.
D. Cooling System is not Cooling Properly
1. Cooling Controller requires maintenance Refer to section- VII.P: Cooling Controller
Setting.
2. Condenser coil is dirty. Refer to section-VII.G: Condenser Coil Cleaning.
3. Refrigerant charges are low. Refer to section-VII.E: Cooling System Pressures.
4. Refer to the enclosed PP Series Temperature Chamber Manual for further
troubleshooting.
E. System Ready Lamp will not illuminate
1. Process Temperature Controller or System Ready Lamp requires maintenance refer to
section-VII.N.
2. Cooling system is not operating correctly see step-C and D above.