Model H1301 Recovery and Recycling System
Installation, Operation and Maintenance Manual
Revision-L September, 2019
Page 32 of 105
V. System Operations and Controls (continued)
D. Automatic System Operation
NOTE: Normal system operation will always be performed in the automatic mode. When
using for the first time after machine installation or, after system evacuation
maintenance operations: complete the Initial System Start-Up procedure section-V.B. of
this manual before operation in the automatic mode. A Complete System Evacuation
section-VII. K, and System Start-Up section-V. B, must be performed before processing a
different type of agent otherwise the agent will be cross contaminated
1. Connect clean dry nitrogen gas to the Nitrogen Supply Port of the machine as per
section-IV.E: Nitrogen Supply. Install a receiving container to the Outlet of the machine
as per section-IV.F: Receiver Storage Container Connections.
WARNING! The receiving container must be capable of containing the quantity of
AGENT to be automatically processed to a fill level no greater than 80%
of container volume: otherwise a dangerous overfill condition of the
receiving container will occur.
CAUTION: Never operate the machine in the Automatic Mode without a receiving
container connected to the Outlet Port of the machine. Total loss of
recycled AGENT will result. Leak test and evacuate the receiving
container and all interconnecting plumbing to the receiving container to a
minimum 2500-micron vacuum level. Failure to evacuate will result in air
and moisture contamination of the receiving container. If the receiving
container already contains clean AGENT: only the interconnecting
plumbing will require evacuation.
CAUTION: Failure to leak test the plumbing connections could result in total loss of
recovered Agent.
2. Remove the valve cap from the nitrogen vent port. Retain this cap for periods of disuse
and maintenance requirements.
3. View the manual controls and verify:
All override switches are in the Auto position
The Cooling System Controller power switch is in the On position
4. Place the front panel power switch to the On position.
5. Adjust the Cooling System Controller set point if necessary to -63F for 1301 operation,
-23F for 1211 or -15F for FM200 operation (reference section-VII.P for detailed
adjustment instructions.)
6. Adjust the Process Temperature Controller alarm set points, (reference section-VII.N)
to the values listed below for the appropriate type of agent.
Alarm #1 Alarm #2
Halon 1301 and FE25 -55 -60
Halon 1211 -15 -20
FM200 -5 -10
7. Adjust the Process Pressure Controller alarm set points, (reference section-VII.M) to
the values listed below for the appropriate type of agent.
Alarm #1 Alarm #2
Halon 1301 and FE25 50 20 to 25
Halon 1211 25 20 to 25
FM200 30 20 to 25