VIII. Trouble Shooting Guide (continued)
F. Machine will not perform Inlet Processing
1. Manual inlet Valve MV-1 is not open: open the valve.
2. Start button has not been depressed: press the Start Button.
3. Front panel toggle switches are not all in the AUTO position: Place all front panel
toggle switches to the AUTO position.
4. Source AGENT container outlet valve is closed: Open the valve and press Start.
5. Source AGENT container is empty: Replace the container.
6. Plumbing from the AGENT source is blocked or restricted: Repair the plumbing.
7. Inlet Vacuum Switch is not reset and requires maintenance refer to section-VII.Q.
8. Any of the following manual valves may be closed Filter Maintenance Valves MV-2
and MV-3, Process Tank Inlet Valve MV-5: Locate and open the closed valve.
9. Inlet Solenoid Valves SV-1 and SV-1A are not opening: refer to section-VIII.J.
10. Inlet Liquid Check Valve CV-1 is stuck closed. Strike the body of the valve sharply
with the handle of a screwdriver. If the valve does not open or continues to
malfunction, replace the valve with part number A4-04-5540-02-0.
11. Process Tank Inlet Check Valve CV-4 is stuck closed. Strike the body of the valve
sharply with the handle of a screwdriver. If the valve does not open or continues to
malfunction, replace the valve with part number A4-04-5530-01-0.
12. Plate Heat Exchanger is blocked with ice. Perform section- VII.J: Heat Exchanger
Evacuation. Examine source AGENT for high water contamination.
13. Inlet Particulate Filter F1 is clogged. Perform section-VII.I: Inlet Particulate Filter
Element Replacement.