Model H1301 Recovery and Recycling System
Installation, Operation and Maintenance Manual
Revision-L September, 2019
Page 25 of 105
V. System Operations and Controls
A. Manual Overrides and System Controls (continued)
25. Process Temperature Controller: Provides a digital display of the machine
processing tank temperature. The controller also is the interface for temperature
information to the system programmable controller and microprocessor unit controller.
The adjustable alarm #1 setting of the controller will control the System Ready Lamp.
26. Pressure Controller: Provides a digital display of the pressure in the processing tank
in absolute pressure per square inch units. The controller also is the interface for
pressure information to the system programmable controller. The adjustable alarm
settings of the controller will control nitrogen venting parameters.
27. Inlet Pressure Gauge: Provides pressure indications of the source container when
the manual inlet valve and the source container outlet valves are both open.
28. Start Push Button: Provides initialization of the automatic operation sequence when
pushed and released.
29. Stop Push Button: Depression of this switch will cease the automatic operation
sequence.
30. Liquid Level Lamps: Provides a visual indication of AGENT levels inside the
processing tank. Lamps of Low, Mid and High will continuously illuminate whenever the
AGENT level in the processing tank is at or above the specific lamp height. Low-Level is
approximately 30 pounds fill, Mid-Level approximately 80 pounds and High-Level is
approximately 105 pounds. The machine automatically processes from Low to Mid
liquid levels. One or more of the liquid level lamps will flash along with the processing
lamp to indicate error conditions.