EasyManua.ls Logo

NHP TemBreak PRO P - P160_BE and P250_BE Information

NHP TemBreak PRO P
66 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Product Information
10
TemBreak PRO P_BE-UM-001-EN V1.3.0
P160_BE and P250_BE Information
Frame / Model
Attribute
Unit
Condition
P160F
P160N
P160H
P250F
P250N
P250H
Number of Poles
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
Nominal current ratings
I
CT
(A)
50°C
40 A
40 A
40 A
40 A
40 A
40 A
Trip unit ratings
100 A
100 A
100 A
100 A
100 A
100 A
160 A
160 A
160 A
160 A
160 A
160 A
250 A
250 A
250 A
Electrical characteristics
Rated maximum operational voltage
U
e
(V)
AC 50/60 Hz
690
690
690
690
690
690
(V)
DC
Rated insulation voltage
U
i
(V)
800
800
800
800
800
800
Rated impulse withstand voltage
U
imp
(kV)
8
8
8
8
8
8
Selectivity category
A
A
A
A
A
A
Rated short time withstand current
I
cw
(kA)
0.4 sec
Ultimate breaking capacity
I
cu
(kA)
690 Vac
6
6
6
6
6
6
(IEC, JIS, AS/NZS)
400 /415 Vac
36
50
70
36
50
70
240 Vac
50
85
85
50
85
85
Service breaking capacity
I
cs
(kA)
690 Vac
6
6
6
6
6
6
(IEC, JIS, AS/NZS)
400 /415 Vac
36
50
50
36
50
50
220 /240 Vac
50
85
85
50
85
85
Protection - Over Current Release types
Std Standard
Opt Optional
Not Available
M Req Module Required
BE 6 dial Adjustable LSI
Std
Std
Std
Std
Std
Std
BE-G 7 dial Adjustable LSIG (Ground Fault)
Std
Std
Std
Std
Std
Std
BE Instantaneous only setting (ICB)
1)
Std
Std
Std
Std
Std
Std
LT Adjustable 40% to 100% in 1% increments
Std
Std
Std
Std
Std
Std
Instantaneous setting independently adjustable
Std
Std
Std
Std
Std
Std
Installation (Std / Opt / ─ )
Std Standard
Opt Optional
Not Available
Front connection (FC)
Std
Std
Std
Std
Std
Std
Extension bar (FB)
Opt
Opt
Opt
Opt
Opt
Opt
Cable tunnel clamp (FW)
Opt
Opt
Opt
Opt
Opt
Opt
Rear Connection (RC)
Opt
Opt
Opt
Opt
Opt
Opt
DIN rail adaptor
Opt
Opt
Opt
Opt
Opt
Opt
Withdrawable mechanism
Opt
Opt
Opt
Opt
Opt
Opt
Plug-in
Opt
Opt
Opt
Opt
Opt
Opt
Reverse supply connection possible to 440V
Yes
Yes
Yes
Yes
Yes
Yes
Dimensions
H
(mm)
165
165
165
165
165
165
W
(mm)
1 pole
2 pole
3 pole
90
90
90
105
105
105
4 pole
120
120
120
140
140
140
D
(mm)
68
68
68
68
68
68
T
(mm)
95.5
95.5
95.5
95.5
95.5
95.5
Weight
W
(kg)
3 pole
1.0
1.0
1.0
1.5
1.5
1.5
4 pole
1.3
1.3
1.3
2
2
2
Operation options (Std / Opt / ─ )
Std Standard
Opt Optional
Not Available
Toggle operation
Std
Std
Std
Std
Std
Std
Extension handle TP-HS/HP or Direct mount T2HB
Opt
Opt
Opt
Opt
Opt
Opt
Motor operation TP-MC
Opt
Opt
Opt
Opt
Opt
Opt
Endurance
Electrical
Cycles
415 Vac
30000
30000
30000
10000
10000
10000
Mechanical
Cycles
50000
50000
50000
30000
30000
30000