EasyManua.ls Logo

NHP TemBreak PRO P - P630_BE Information

NHP TemBreak PRO P
66 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Product Information
12
TemBreak PRO P_BE-UM-001-EN V1.3.0
P630_BE Information
Frame / Model
Attribute
Unit
Condition
P630F
P630N
P630H
P630S
Number of Poles
3, 4
3, 4
3, 4
3, 4
Nominal current ratings
I
CT
(A)
50°C
630A
630A
630A
630A
Trip unit ratings
Calibration
Electrical characteristics
Rated maximum operational voltage
U
e
(V)
AC 50/60 Hz
690
690
690
690
(V)
DC
Rated insulation voltage
U
i
(V)
800
800
800
800
Rated impulse withstand voltage
U
imp
(kV)
8
8
8
8
Selectivity category
A
A
A
A
Rated short time withstand current
I
cw
(kA)
0.4 sec
Ultimate breaking capacity
I
cu
(kA)
690 Vac
7
12
12
12
(IEC, JIS, AS/NZS)
400 /415 Vac
36
50
70
110
240 Vac
50
85
100
125
Service breaking capacity
I
cs
(kA)
690 Vac
7
12
12
12
(IEC, JIS, AS/NZS)
400 /415 Vac
36
50
70
110
220 /240 Vac
50
85
100
125
Protection - Over Current Release types
Std Standard
Opt Optional
Not Available
M Req Module Required
BE 6 dial Adjustable LSI
Std
Std
Std
Std
BE-G 7 dial Adjustable LSIG (Ground Fault)
Std
Std
Std
Std
BE Instantaneous only setting (ICB)
1)
Std
Std
Std
Std
LT Adjustable 40% to 100% in 1% increments
Std
Std
Std
Std
Instantaneous setting independently adjustable
Std
Std
Std
Std
Installation (Std / Opt / ─ )
Std Standard
Opt Optional
Not Available
Front connection (FC)
Std
Std
Std
Std
Extension bar (FB)
Std
Std
Std
Std
Cable tunnel clamp (FW)
Opt
Opt
Opt
Opt
Rear connection (RC)
Opt
Opt
Opt
Opt
DIN rail adaptor
Withdrawable mechanism
Opt
Opt
Opt
Opt
Plug-in
Opt
Opt
Opt
Opt
Reverse supply connection possible to 440V
Yes
Yes
Yes
Yes
Dimensions
H
(mm)
260
260
260
260
W
(mm)
1 pole
2 pole
3 pole
140
140
140
140
4 pole
185
185
185
185
D
(mm)
103
103
103
103
T
(mm)
145
145
145
145
Weight
W
(kg)
3 pole
5.0
5.0
5.0
5.0
4 pole
6.6
6.6
6.6
6.6
Operation options (Std / Opt / ─ )
Std Standard
Opt Optional
Not Available
Toggle operation
Std
Std
Std
Std
Extension handle TP-HS/HP or Direct mount T2HB
Opt
Opt
Opt
Opt
Motor operation TP-MC
Opt
Opt
Opt
Opt
Endurance
Electrical
Cycles
415 Vac
4000
4000
4000
4000
Mechanical
Cycles
15000
15000
15000
15000

Table of Contents

Related product manuals