Are the service valves fully open?
YES
YES
YES
Is the electronic expansion valve
correctly connected?
Open the service valves.
Is the high pressure switch ( 63H1)
correctly connected?
Has the high pressure switch
(63H1) been activated?
Action.
NO
NO
NO
1. During cooling:
- Does the fan motor run?
- Is the air flow obstructed?
- Is the installation space
sufficient?
2. During heating:
- Is the indoor module's sensor for
the heat exchanger correctly
connected?
- Is the filter blocked?
If the voltage supply to the outdoor unit is switched off and on too quickly, 220
may be displayed. This is normal.
Action.
NO
YES
YES
Is there DC 230 V on connector
CNW
On the control board (PWB1 )
between red and white cable.
Defective control board - replace.
Check fuse (4A) and cable.
NO