Control
31
For the Installer
FIGHTER 1220
Outside temperature
Menu 4.2 Return
Pressing the enter button returns you to menu 4.0.
Menu 4.1 Outdoor avg. temp.
Average outdoor temperature during the last 24 hours
.
Return
4.2
Outdoor avg. temp.
4.1
N
Brine flow/return
Menu 5.5 Status
Shows the compressor status for the heat pump.
Start in XX minutes, means the compressor will start
as soon as the time condition permits.
Inactive means the compressor is at a stand still.
Compr. On means the compressor is running.
Brine pump On means the brine pump is running.
Start in 5 min
Status
5.5
Menu 5.3 Time between starts
Time between compressor starts is set here. The val-
ue is adjustable between 10 and 60.
20 min
Time between starts
5.3
N
N
Menu 5.4 Compr. starts at
How low the degree minutes may drop before the a
compressor start can take place is set here. The value
is adjustable between -5 and -250.
-60
Compr. starts at
5.4
N
Menu 5.1 Brine ret. temp/MIN
The lowest brine temperature is set here. The value is
adjustable between 12 and -11 minutes. When a low-
er temperature is selected OFF is shown, which
means the heat pump never gives an alarm for a low
brine temperature.
-4.0 (OFF)°C
Brine ret. temp/MIN
5.1
N
Menu 5.2 Autoreset brinealarm
Automatic restart after an HF alarm, when the temper-
ature rises 3 °C above the selected alarm level (menu
5.1) for the brine return is selected here. The value is
adjustable On or Off.
Off
Autoreset brinealarm
5.2
N