4.4.4 Fuse Selection for Type 2 Coordination
Type 2 coordination is achieved by using semiconductor fuses. These fuses must be able to carry motor start current
and have a total clearing I
2
t less than the I
2
t of the soft starter SCRs.
When selecting semiconductor fuses for Digistart D3, use the I
2
t values in the table.
For further information on selecting semiconductor fuses, contact your local distributor.
4.4.5 Control supply fuses
The following table lists the recommended control supply fuses. It is recommended that you use slow blow fuses
which allow a 10A, 0.01 second surge.