58 Digistart D3: User Guide
Issue: G
8.5 Quick setup details
To access the Quick Setup Menu, press the M button and select Quick Setup Menu.
The Quick Setup Menu makes it easy to configure the Digistart D3 for common applications. The Digistart D3 selects
the parameters relevant to the application and suggests a typical setting, and you can adjust each parameter to suit
your exact requirements.
Always set Pr 1A Motor Full Load Current to match the motor's nameplate full load current. The suggested value is
the starter's minimum full load current.
Start Mode
Adaptive Start Profile
Start Ramp Time
Stop Mode
Adaptive Stop Profile
2A
2E
2D
2H
2K
Adaptive Control
Early Acceleration
10 seconds
Adaptive Control
Late Deceleration
Start Mode
Adaptive Start Profile
Start Ramp Time
Stop Mode
Adaptive Stop Profile
2A
2E
2D
2H
2K
Adaptive Control
Early Acceleration
5 seconds
Adaptive Control
Late Deceleration
Start Mode
2A
Constant Current
Start Mode
Adaptive Start Profile
Start Ramp Time
Excess Start Time
2A
2E
2D
5A
Adaptive Control
Constant Acceleration
20 seconds
30 seconds
Start Mode
Start Ramp Time
2A
2D
Constant Current
5 seconds
Start Mode
Start Ramp Time
2A
2D
Constant Current
5 seconds
Start Mode
Start Ramp Time
Current Limit
Stop Mode
Adaptive Stop Profile
2A
2D
2B
2H
2K
Constant Current
5 seconds
400%
Adaptive Control
Constant Deceleration
Start Mode
Start Ramp Time
Current Limit
Excess Start Time
2A
2D
2B
5A
Constant Current
10 seconds
400%
30 seconds