NE200&300 Quick Start Guide
51
Code
Description Setting range Default
Modify
Modbus
Address
F8.02
Analog PID
digital setup
0.0
999.9 50 0902H
F8.03
Analog closed
loop measuring
range
1.0
999.9 100 0903H
F8.04
PID action
direction
0: Positive
1: Negative
0 0904H
F8.05
PID proportional
gain 1 (KP1)
0.1
9.9 1 0905H
F8.06
PID integration
time 1
0
100s
10s
3s
0906H
F8.07
PID differential
time 1
0.00
1.00s 0.00s 0907H
F8.08
PID proportional
gain 2 (KP2)
0.1
9.9 1 0908H
F8.09
PID integration
time 2
0.0
100.0s 10.0s 0909H
F8.10
PID differential
time 2
0.00
1.00s 0.00s 090AH
F8.11
PID parameters
switching
0: No switching, use
the first group
parameters
0 090BH 1: switching by
terminal
2: auto-switching by
deviation
F8.12
PID parameter
switching
Deviation 1
0.0
999.9 20 090CH
F8.13
PID parameter
switching
Deviation 2
0.0
999.9 80 090DH
F8.14
PID delay time
constant
0.0
100.0s 0.0s 090EH
F8.15
Deviation limit 0.0
999.9 0.2 090FH