NE200&300 Quick Start Guide
28
Code
Description Setting range Default
Modify
Modbus
Address
DC brake
current at stop
Type G: 0.0~100.0% rated
current
Type P: 0.0~80.0% rated
current
0.00%
020BH
F1.12
DC brake time
at stop
0.0
30.0s 0.0s 020CH
F1.13
Energy
consumption
brake validity
0: Disabled
0 020DH
1: Enabled
F1.14
Energy
consumption
brake action
voltage
380V: 650~750V 700V
020EH
220V: 360~390V 380V
F1.15
Power failure
and fault restart
0: Disable
1: Enabled for power
failure
0 020FH
2: Enabled for fault
3: Enabled for both
Note: Power recovery
restart is only valid for
terminal 2-wires mode.
Fault restart is invalid for
under-voltage fault.
F1.16
Waiting time
for restart
0.0
3600s 2.0s 0210H
F1.18
Rotational
speed tracking
direction
inspection
0: Disable
1: Enable
0 0212H
F1.19
Rotational
speed tracking
direction
inspection time
10~1000ms 50ms 0213H
Group F2: Auxiliary running function