NE200/300 Series Drive User Manual
104 Chapter 6 Parameter description
F0.09 UP/DOWN data saving selection Range: 020
0: Setting data saved in power failure
This option means the frequency upon power recovery is the
frequency after Up/Down setting before power failure.
1: Setting not saved in power failure
This option means that the frequency upon power recovery is the
preset Up/Down frequency value in F0.06. The Up/Down modification
before power failure is cleared.
2:
Setting cleared to 0 after stop
The Up/Down setting during running will be cleared after the drive stop.
The frequency upon restart will be preset Up/Down frequency value in
F0.06. And the modification part is cleared.
F0.10 Basic frequency Range: 0.10550.0Hz50.00Hz
F0.11 Max frequency
Range: MAX [50.00Hz, Freq. upper limit,
Reference frequency] 550.0Hz
50.00Hz
F0.12 Freq. upper limit Range: Freq. lower limitMax freq.
50.00Hz
F0.13 Freq. lower limit Range: 0.00Frequency upper limit
0.00Hz
F0.14 Max output voltage
Range: 110440VDepend on model
The basic frequency (F
b
) is the Min. output frequency when the drive
output the Max. voltage. Usually, the motor rated frequency can be treated
as basic frequency.
The max frequency (F
max
) is the highest frequency that the drive can
output.