NE200/300 Series Drive User Manual
Chapter 6 Parameter description 103
source switching” setting is invalid or the terminal has no setting of
“Freq. source switching”, the frequency reference is determined by
frequency ref.-1.
4: Terminal switching between (Freq. ref.1+ Freq. ref.2) & Freq. ref.1
When the “Freq. source switching” terminal is invalid, the frequency
reference is determined by Freq. ref.1+ Freq. ref.2. When the “Freq.
source switching” terminal is active, the frequency reference is
determined by Freq. ref.1
F0.06 UP/DOWN Preset Freq. Range: 0.00 ~ Max frequency
【50.00Hz】
When the frequency source has selected “Digital setup” or “Terminals
UP/DN”, this function code is the initial value of frequency digital setup of
the drive.
F0.07 Terminal UP/DOWN rate Range: 0.01~50.00Hz/s【1.00Hz/s】
Terminal UP/DOWN rate is the changing rate in terminal or keypad ∧
and ∨ setting.
F0.08 UP/DOWN function source select Range: 0~2【1】
This parameter is used to select the UP/DOWN channel in Digital
frequency reference setting.
0: Active in both keypad and terminal UP/DOWN
1: Active only in keypad UP/DOWN
2: Active only in terminal UP/DOWN