NE200/300 Series Drive User Manual
102 Chapter 6 Parameter description
options. If the terminal has selected multi-speed and active, the Freq.
ref. 1 is determined by multi-speed no matter what value has F0.03
setup.
In option of Freq. ref. 1+ the Freq. ref. 2, the UP/DOWN digital setting
of Freq. ref. 1 will be Up/Down overlapped on Frequency ref.-2. And the
F0.06 Up/Down preset value is invalid.
Pulse reference can only be input from the multifunction input terminals
X4 or X5.
F0.05 Frequency setting selection
Range: 06 0
This parameter is used to select the frequency reference channel. The
frequency reference is realized through combination of frequency setting 1
and frequency setting 2.
0: Frequency reference 1
The frequency reference is determined by the selected channel of freq.
ref-1.
1: Frequency reference 2
The frequency reference is determined by the selected channel of freq.
ref-2
2: Frequency reference 1 + Frequency reference 2
5: MIN (Frequency reference 1, Frequency reference 2)
6: MAX (Frequency reference 1, Frequency reference 2)
The frequency reference is determined by frequency setting 1 and
frequency setting 2 after the corresponding arithmetic.
3: Terminal switching between Freq. ref.1 & Freq. ref.2
The frequency reference can switch between the Frequency ref. 1 and
Frequency ref.2 through the multifunction input terminal. When the
terminal with “Freq. source switching” setting is active, the frequency
reference is determined by freq. ref.-2. When the terminal with “Freq.