NE200/300 Series Drive User Manual
Chapter 6 Parameter description 113
For large rotary inertia applications where rapid stop is required, the
drive can be equipped with matched braking unit and braking resistors and
proper braking parameters setting to realize fast braking and stop.
Note: For NE300, is only valid for 22kW and above.
F1.14 Energy consumption brake
action voltage
Range: 380V: 650~750V【700V】
220V: 360~390V【380V】
This parameter is to set the action voltage of DC bus for energy
consumption brake. The proper setting can get effective brake of the load.
F1.15 Power failure and fault restart
Range: 0~3【0】
0: Disable
Drive will not automatically restart after power recovery until run
command is given.
1: Enabled for power failure
In case of power failure and power-on again, if STOP command is not
given during restart-waiting time (F1.16), drive will restart
automatically;
2: Enabled for fault
After drive get faults during running, if the stop command is not given
during fault stage or restart-waiting time (F1.16), the drive will restart
automatically after fault reset.
3: Enabled for both power failure and fault
The automatic restart function is enabled for both power failure
recovery and faults reset situations as explained above.
Note:
The user shall be very caution in using this function. The inappropriate
setting might cause damage of machinery or injury of human.
F1.16 Waiting time for restart Range: 0.0~3600s【0.0s】