NE200/300 Series Drive User Manual
Chapter 6 Parameter description 115
takes to accelerate form 0Hz to Max. output frequency F0.11; the jog
deceleration time refers to the time the drive takes to decelerate from Max.
output frequency F0.11 to 0Hz.
Note:
When the jog Acc./Dec. time is set to 0, the drive jog deceleration mode
is “coast to stop”.
F2.03 Acceleration time2
Range:
0.1~360.0s6.0s
0.0~3600.0s
20.0s
F2.04 Deceleration time2
Range:
0.1~360.0s6.0s
0.0~3600.0s
20.0s
F2.05 Acceleration time3
Range:
0.1~360.0s6.0s
0.0~3600.0s
20.0s
F2.06 Deceleration time3
Range:
0.1~360.0s6.0s
0.0~3600.0s
20.0s
F2.07 Acceleration time4
Range:
0.1~360.0s6.0s
0.0~3600.0s
20.0s
F2.08 Deceleration time4
Range:
0.1~360.0s6.0s
0.0~3600.0s
20.0s
These parameters are to define Acc/Dec time 2, 3 and 4 respectively
(Acc/Dec time 1 is defined in F0.19 and F0.20). Acc/Dec time 1, 2, 3 and 4
can be selected via external multifunction input terminals. If all terminals
related with Acc/Dec time are invalid, the drive will take Acc/Dec time 1 as
Acc/Dec time. However, when the drive chooses PLC or JOG operation,
Acc/Dec time will not be controlled by external terminals, but be set by
parameter of PLC or JOG.
F2.09 Skip freq. 1
Range: 0.00~300.0Hz
0.00Hz
F2.09 Skip freq
.
1
Rang
e: 0.00~320.0Hz
0.00Hz
F2.10 Skip freq
.
2
Range: 0.00~320.0Hz
0.00Hz

Table of Contents