F2.11 Skip frequency amplitude Range: 0.00~15.00Hz【0.00Hz】
To avoid mechanical resonant, the drive can skip over some running
points, which is called skip frequency. As shown in Fig.6-5.
NE300 drives can set two skip frequency points, and the skip frequency
amplitude can overlap or nesting. If overlapped, the range broadens. When
all, skip-freq. points value, are set to 0.00 Hz, the jump function will be
disabled. Only one, skip frequency1, point for NE200.
Fig.6-5 Skip Frequency
F2.12 Anti-reverse control Range: 0~1【0】
For some equipment, reverse operation may cause equipment damage.
This function can be used to prevent reverse operation.
0: Reverse rotation allowed
1: Reverse rotation not allowed
F2.13 Fwd/ Rev switch dead-zone
time
Range: 0.0~3600s【0.0s】
It refers to the transition waiting time at zero frequency in process of
rotation direction switching, i.e. from forward to reverse or from reverse to
forward, as shown Fig.6-6.