NE200/300 Series Drive User Manual
Chapter 6 Parameter description 117
Fig.6-6 FWD/REV switching
F2.14 Freq. lower-limit treatment Range: 0~1【0】
This parameter is used to select the running status of the drive when the
setup frequency is lower than the frequency lower limit.
0: Run with frequency lower limit
1: Zero frequency operation
F2.15 Reserved
Energy-saving control select
0: Disable 1: Enable
‘0’ means the energy-saving control mode is disabled.
‘1’ means the energy-saving control mode is enabled.
To adjust the output current to degrease the energy-saving of motor by
inspecting the current of load while the motor is working in no-load or
light-load status.
Note:
This function is enabled while controlled by V/F mode.
F2.17 AVR function Range: 0~2【2】
0: Disabled