NE200/300 Series Drive User Manual
Chapter 6 Parameter description 143
Value
Function Description
26
External fault normally
open
After the external fault signal is sent to the
drive, the drive reports fault and stops.
27
External fault normally
closed
28
Run command switching
to terminal
When Run command (F0.02) is 0 or 2, this
terminal forces the run command switching to
terminal control.
29
Run command switching
to Keypad
When Run command (F0.02) is 1 or 2, this
terminal forces the run command switching to
keypad control.
30
External stop terminal;
same to STOP key in
keypad control mode.
This is to define an external stop terminal. In
keypad control mode, this terminal can stop
the drive. It is same as STOP key on keypad.
31 Reserved Reserved
32 PLC status reset Drive reset to the first step of PLC running.
33 Wobble freq. pause
The drive pause at the present frequency.
Once this terminal is disabled, the drive
resumes the wobble frequency running.
34 Wobble freq. status reset
The drive returns to wobble center frequency.
35 PID pause
PID is inactive temporarily, and the drive
maintains the current frequency output.
36
PID parameters
switching
If the terminal is valid, PID control switches to
second group PID parameters.
37 PID direction reversion
If this terminal is enabled, PID action
direction is opposite to the direction set in
F8.04.
38 Timing drive input
If the terminal is valid, drive starts the timing,
otherwise zero-clear.
39 Counter signal input The input terminal of counting pulse.
40 Counter clear Clear the counter status.
41
③
Actual length clear
When the function terminal is enabled, actual
length in fixed length control will be cleared to
zero.
42 FWD running (FWD NC)
Control the drive forward or reversed by
external terminals.
43 REV running (REV NC)
44 HLD (Normally Open) Running signal self-hold terminal, refer to