NE200/300 Series Drive User Manual
Chapter 5 List of Parameters 61
Code
Description Setting range Default
Modify
Modbus
Address
speed tracking
direction
inspection time
Group F2: Auxiliary running function
Code
Description Setting range Default Modify
Modbus
Address
F2.00
Jog running freq.
0.0
~
50.00Hz 5.00Hz ○ 0300H
F2.01
Jog Acc. time
0.1
~
360.0s
0.0~3600.0s
6.00s
20.0s
○ 0301H
F2.02
Jog Dec. time
0.1
~
360.0s
0.0~3600.0s
6.00s
20.0s
○ 0302H
F2.03
0.1
~
360.0s
0.0~3600.0s
6.00s
20.0s
○ 0303H
F2.04
Dec. time2
0.1
~
360.0s
0.0~3600.0s
6.00s
20.0s
○ 0304H
F2.05
0.1
~
360.0s
0.0~3600.0s
6.00s
20.0s
○ 0305H
F2.06
Dec. time3
0.1
~
360.0s
0.0~3600.0s
6.00s
20.0s
○ 0306H
F2.07
0.1
~
360.0s
0.0~3600.0s
6.00s
20.0s
○ 0307H
F2.08
Dec. time4
0.1
~
360.0s
0.0~3600.0s
6.00s
20.0s
○ 0308H
F2.09
②
Reserved Reserved Reserved
Reserv
ed
0309H
Skip freq. 1 0.00~320.0Hz 0.00Hz × 0309H
F2.10
Skip freq. 2
0.00
~
320.0Hz 0.00Hz × 030AH
F2.11
Skip freq.
amplitude
0.00
~
15.00Hz 0.00Hz
× 030BH
F2.12
-Reverse
control
0: Reverse rotation
allowed
0 ○ 030CH
1: Reverse rotation not
allowed
F2.13
Fwd/ Rev switch 0.0
~
3600s 0.0s ○ 030DH