NE200/300 Series Drive User Manual
Chapter 5 List of Parameters 83
Code
Description Setting range Default
Modify
Modbus
Address
selection 2: Pulse input
3: serial
communication
4: AI1-AI2
5: AI1+AI2
6: MAX(AI1, AI2)
7: MIN(AI1, AI2)
F8.02
Analog PID
digital setup
0.0
999.9 50 0902H
F8.03
Analog closed
loop measuring
range
1.0
999.9 100 0903H
F8.04
PID action
direction
0: Positive
1: Negative
0 0904H
F8.05
PID proportional
gain 1 (KP1)
0.1
9.9 1 0905H
F8.06
PID integration
time 1
0
100s
10s
3s
0906H
F8.07
PID differential
time 1
0.00
1.00s 0.00s 0907H
F8.08
PID proportional
gain 2 (KP2)
0.1
9.9 1 0908H
F8.09
PID integration
time 2
0.0
100.0s 10.0s 0909H
F8.10
PID differential
time 2
0.00
1.00s 0.00s 090AH
F8.11
PID parameters
switching
0: No switching, use
the first group
parameters
0 090BH 1: switching by
terminal
2: auto-switching by
deviation
F8.12
PID parameter
switching
0.0
999.9 20 090CH