NE200/300 Series Drive User Manual
84 Chapter 5 List of Parameters
Code
Description Setting range Default
Modify
Modbus
Address
Deviation 1
F8.13
PID parameter
switching
Deviation 2
0.0
999.9 80 090DH
F8.14
PID delay time
constant
0.0
100.0s 0.0s 090EH
F8.15
Deviation limit 0.0
999.9 0.2 090FH
F8.16
PID output
positive limit
0.0~320.0Hz
0.0
600.0Hz
50.00Hz
0910H
F8.17
PID output
negative limit
0.00
550.0Hz 0.00Hz
0911H
F8.18
PID preset freq. 0.00
550.0Hz 0.00Hz
× 0912H
F8.19
Hold time of PID
preset frequency
0.0
3600s 0.0s × 0913H
F8.20
Enable
dormancy
0: Disabled
1: Enabled
0 × 0914H
F8.21
Dormancy delay
0
999s 120s 0915H
F8.22
Dormancy
threshold
0.0
320.0Hz 20.0Hz
0916H
F8.23
Awaken
threshold
0.0~100.0%
(relative to pre-set
value)
80.00%
0917H
F8.24
PID feedback
offline detection
range
0.0~100.0%
(relative to feedback
measuring range,
0.0% no detection)
0.0% 0918H
F8.25
PID feedback
offline detection
time
0.0~50.0s 2.0s 0919H
F8.26
PID feedback
offline detection
Min. Freq.
0.00~50.00Hz 10.00Hz
091AH
Group F9: Multi-step speed and PLC

Table of Contents