NE200/300 Series Drive User Manual
Chapter 5 List of Parameters 87
Code
Description Setting range Default
Mod
ify
Modbus
Addres
s
F9.34
Multi-step freq.15 0.00
Max frequency
50.00 Hz
0A22H
F9.35
PLC Multi-step
Freq.1 selection
0:Multi-step digital
setting
0
0A23H
1: AI1
2: AI2
F9.36
PLC Multi-step
Freq.7 selection
3: keypad
potentiometer
0
0A24H
4: Pulse input
Group FA: Wobble Frequency
Code
Description Setting range Default
Modify
Modbus
Address
FA.00
Wobble
amplitude
0.0~50.0% 0.0% 0B00H
FA.01
Jitter frequency 0.0~50.0%(to FA.00) 0.0% 0B01H
FA.02
Jitter Time 5
50ms 5ms 0B02H
FA.03
Wobble freq. up
time
0.1
999.9s 5.0s 0B03H
FA.04
Wobble freq.
down time
0.1
999.9s 5.0s 0B04H
FA.05
Amplitude mode
0: Relative to the
central freq.
0 0B05H
1: Relative to Max.
frequency
Group Fb: Fixed Length
Code
Description Setting range Default
Modify
Modbus
Address
Fb.00
Preset length 0
65530 0 0C00H
Fb.01
Actual length 0
65530 0 * 0C01H
Fb.02
Pulses number
per unit
0.1
6553.0 100 0C02H
Group FC: Protection and Fault Parameters