EasyManua.ls Logo

nord NORDAC PRO SK 511E Series - Page 105

nord NORDAC PRO SK 511E Series
218 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 Parameters
BU 0505 EN-3021 105
P209
No load current
(No load current)
S P
0.0 ... 1000.0 A
{ see information }
This value is always calculated automatically from the motor data if there is a change in the
parameter >cos ϕ< P206 and the parameter >Nominal current< P203.
NOTE: If the value is to be entered directly, then it must be set as the last motor data. This is
the only way to ensure that the value will not be overwritten.
Information
Default setting
The default setting is dependent upon the FI nominal power and the setting in P200.
Pos: 159 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P200- P299/Parameter P210 Sta tischer Boost @ 0\mod_132759015 6790_388.docx @ 8094 @ @ 1
P210
Static boost
(Static boost)
S P
0 ... 400 %
{ 100 }
The static boost affects the current that generates the magnetic field. This is equivalent to the no
load current of the respective motor and is therefore load-independent
. The no load current is
calculated using the motor data. The factory setting of 100% is sufficient for normal applications.
Pos: 160 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P200- P299/Parameter P211 Dy namischer Boost @ 0\mod_1327590 224915_388.doc x @ 8117 @ @ 1
P211
Dynamic boost
(Dynamic boost)
S P
0 ... 150 %
{ 100 }
The dynamic boost affects the torque generating current and is therefore a load-dependent
parameter. The factory 100% setting is also sufficient for typical applications.
Too high a value can lead to overcurrent in the FI. Under load therefore, the output voltage will be
raised too sharply. Too low a value will lead to insufficient torque.
Pos: 161 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P200- P299/Parameter P212 Sc hlupfkompensation @ 0\mod _1327590275572_388.doc x @ 8140 @ @ 1
P212
Slip compensation
(Slip compensation)
S P
0 ... 150%
{ 100 }
The slip compensation increases the output
frequency, dependent on load, to keep the
asynchronous motor speed approximately constant.
The factory setting of 100% is optimal when using DC asynchronous motors and correct motor data
has been set.
If several motors (different loads or outputs) are operated with one FI, the slip compensation P212
must be set to 0%. This excludes any negative influences. With PMSM motors, the parameter must
be left at the factory setting.
Pos: 162 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P200- P299/Parameter P213 Verst. I SD-Regelung @ 0\mod_132759032 3026_388.docx @ 8163 @ @ 1
P213
ISD ctrl. loop gain
(Amplification of ISD control)
S P
25 ... 400 %
{ 100 }
This parameter influences the control dynamics of the FI current vector control (ISD control). Higher
settings make the controller faster, lower settings slower.
Dependent on application type, this parameter can be altered, e.g. to avoid unstable operation.
Pos: 163 /Anleitun gen/Elektronik/F U und Starter/5. Parameter /Parameterauflis tung (P000 ...)/ P200-P299/Parameter P214 Vor halt Drehmoment @ 0\mod_13275 90368794_388.doc x @ 8186 @ @ 1
P214
Torque precontrol
(Torque precontrol)
S P
-200 ... 200 %
{ 0 }
This function allows a value for the expected torque requirement to be set in the controller. This
function can be used in lifting applications for a better load transfer during start-up.
NOTE:
Motor torques (with rotation field right) are entered with a positive sign, generator
torques are entered with a negative sign.
The reverse applies for the counter
clockwise rotation.
Pos: 164 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P200- P299/Parameter P215 Boos t Vorhalt @ 0\mod_13275904 15702_388.docx @ 8209 @ @ 1

Table of Contents

Related product manuals