SK 54xE – Users Manual for Frequency Inverters
124 BU 0505 EN-3021
e
The actual apparent power of the motor as calculated by the device
The actual effective power calculated by the device
The actual torque calculated by the device
The actual field in the motor, as calculated by the device
The analog voltage is proportional to the output frequency of the device, whereby the null point is
shifted to 5 V. For rotation to the right, values between 5 V and 10 V are output, and for rotation to
the left values between 5 V and 0 V.
This is the synchronous rotation speed calculated by the FI, based on the current setpoint, where
the null point has been shifted to 5 V. For rotation to the right, values from 5 V to 10 V are output
and for rotation to the left, values from 5 V to 0 V.
The measured speed is output via this function if servo mode is used.
Is the actual torque calculated by the FI, whereby the null point is shifted to 5 V. For drive torques,
values between 5 V and 10 V are output, and for generator torque, values between 5 V and 0 V.
Setpoint freq. before ramp
displays the frequency produced by any upstream controllers (ISD, PID, etc.). This is then the
setpoint frequency for the power stage after it has been adjusted by the acceleration or braking
ramp (P102, P103).
the analog output is controlled via a bus system. The process data is directly transferred (P546,
P547, P548 = 20).
Freq. of setpt. source, "Frequency of setpoint source" (above SW version 1.6)
NOTE: overview of various setpoints: (please see chapter 8.7 "Standardisation of setpoint / target
values").
Pos: 247 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P400- P499/Parameter P418 – Liste d er digitalen Funktione n der analogen Ausgänge @ 0\mo d_1327940847568_38 8.docx @ 9743 @ 5 @ 1
List of possible digital functions of the analog outputs
All relay functions described in parameter P434 can also be transferred via the analog output. If a
condition has been fulfilled, then there will be 10 V at the output terminals. Negation of the function
can be specified in parameter P419.
Frequency and setpoint source
Frequency limit
BusIO In Bit 0
Warning
BusIO In Bit 3
Motor overtemperature warning
Torque current limit active
BusIO In Bit 6
Generator torque current limit
Output via Bus (if P546, P547 or P548 = 19), BUS Bit 4
then controls the analog output.
Pos: 248 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterüberschr ift - Fortsetzung Tabel le @ 1\mod_1331566123473 _388.docx @ 18340 @ @ 1