EasyManua.ls Logo

nord NORDAC PRO SK 511E Series - Page 124

nord NORDAC PRO SK 511E Series
218 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SK 54xEUsers Manual for Frequency Inverters
124 BU 0505 EN-3021
Valu
e
Function
Description
08
Apparent power
The actual apparent power of the motor as calculated by the device
09
Effective power
The actual effective power calculated by the device
10
Torque [%]
The actual torque calculated by the device
11
Field [%]
The actual field in the motor, as calculated by the device
12
Actual frequency ±
The analog voltage is proportional to the output frequency of the device, whereby the null point is
shifted to 5 V. For rotation to the right, values between 5 V and 10 V are output, and for rotation to
the left values between 5 V and 0 V.
13
Actual speed ±
This is the synchronous rotation speed calculated by the FI, based on the current setpoint, where
the null point has been shifted to 5 V. For rotation to the right, values from 5 V to 10 V are output
and for rotation to the left, values from 5 V to 0 V.
The measured speed is output via this function if servo mode is used.
14
Torque [%] ±
Is the actual torque calculated by the FI, whereby the null point is shifted to 5 V. For drive torques,
values between 5 V and 10 V are output, and for generator torque, values between 5 V and 0 V.
30
Setpoint freq. before ramp
displays the frequency produced by any upstream controllers (ISD, PID, etc.). This is then the
setpoint frequency for the power stage after it has been adjusted by the acceleration or braking
ramp (P102, P103).
31
Output via BUS PZD
the analog output is controlled via a bus system. The process data is directly transferred (P546,
P547, P548 = 20).
33
Freq. of setpt. source, "Frequency of setpoint source" (above SW version 1.6)
60
Reserved
(above SK540E
BU 0550)
NOTE: overview of various setpoints: (please see chapter 8.7 "Standardisation of setpoint / target
values").
Pos: 247 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P400- P499/Parameter P418 Liste d er digitalen Funktione n der analogen Ausgänge @ 0\mo d_1327940847568_38 8.docx @ 9743 @ 5 @ 1
List of possible digital functions of the analog outputs
All relay functions described in parameter P434 can also be transferred via the analog output. If a
condition has been fulfilled, then there will be 10 V at the output terminals. Negation of the function
can be specified in parameter P419.
Value
Function
Value
Function
15
External brake
32
FI ready
16
Inverter working
33
Frequency and setpoint source
17
Current limit
34
... 40 reserved (POSICON
BU 0510)
18
Torque current limit
41
... 43 reserved
19
Frequency limit
44
BusIO In Bit 0
20
Setpoint reached
45
BusIO In Bit 1
21
Fault
46
BusIO In Bit 2
22
Warning
47
BusIO In Bit 3
23
Overcurrent warning
48
BusIO In Bit 4
24
Motor overtemperature warning
49
BusIO In Bit 5
25
Torque current limit active
50
BusIO In Bit 6
26
Value of P541
51
BusIO In Bit 7
27
Generator torque current limit
52
Value from Bus setpoint
Output via Bus (if P546, P547 or P548 = 19), BUS Bit 4
then controls the analog output.
28
... 29 reserved
60
reserved (PLC
BU 0550)
Pos: 248 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterüberschr ift - Fortsetzung Tabel le @ 1\mod_1331566123473 _388.docx @ 18340 @ @ 1

Table of Contents

Related product manuals