List of the possible functions of digital inputs
The inverter delivers an output signal with the rotation field right if a positive
setpoint is present. 0 → 1 Flank (P428 = 0)
The inverter delivers an output signal with the rotation field left if a positive
setpoint is present. 0 → 1 Flank (P428 = 0)
If the drive is to start up automatically when the mains is switched on (P428 = 1) a permanent High level for enabling must be provided (bridge
between DIN1 and the control voltage output).
If the functions "Enable right" and "Enable left" are actuated simultaneously, the FI is blocked.
If the frequency controller is in fault status but the cause of the fault no longer exists, the error message is acknowledged with a 1 → 0 flank .
Change of rotation direction
Causes the rotation field to change direction, combined with Enable right or left.
04 Fixed frequency 1
1
The frequency from P429 is added to the actual setpoint value. High
The frequency from P430 is added to the actual setpoint value.
The frequency from P431 is added to the actual setpoint value.
1
The frequency from P432 is added to the actual setpoint value.
If several fixed frequencies are actuated at the same time, then they are added with the correct sign. In addition, the analogue setpoint (P400)
and if necessary the minimum frequency (P104) are added.
sets
First Bit of the parameter set switch over, selection of the active parameter set
1…4 (P100).
During the acceleration or deceleration phase, a Low level will cause the actual
output frequency to be "held". A high level allows the ramp to proceed.
The FI output voltage is switched off; the motor runs down freely.
The FI reduces the frequency according to the programmed fast stop time from
P426.
Error acknowledgement with an external signal. If this function is not
programmed, an fault can also be acknowledged by a low enable setting
(P506).
Flank
Analog evaluation of signal present. Switching threshold approx. 2.5 V, Switch-
off delay = 2 sec, warning after 1 sec.
NOTE: Function 13 can only be used via DIN 5 up to SK 535E, sizes 1 - 4!
For SK 54xE and sizes above Size 5, there is a separate connection which
cannot be deactivated. If the motor is equipped with a thermistor, for these
devices both terminals must be bridged in order to deactivate the function
(status as delivered).
2, 4
With Bus system control, low level switches the control to control via control
terminals.
The fixed frequency value can be adjusted using the HIGHER/LOWER and
ENTER keys (P113), if control is via the ControlBox or ParameterBox.
As in setting 09, however, the frequency is not maintained below the minimum
frequency P104 and above the maximum frequency P105.
Second Bit of the parameter set switch over, selection of the active parameter
set 1…4 (P100).
18 Watchdog
2
Input must see a High flank cyclically (P460), otherwise error E012 will cause a
shutdown. Function starts with the 1st high flank.
01
Flank
Analog input switch-on and switch-
off 1/2 (high = ON) The low signal sets the
analog input to 0 % which does not lead to shut-
frequency (P104) > than the absolute minimum frequency (P505).
High
20 Setpoint 2 on/off
The frequency from P433 is added to the actual setpoint value.
Reserved for POSICON (BU 0510)
26 ... 29 impulse functions:
30 Disable PID Switching the PID controller / process controller function on and off (high = ON) High
Blocks the >Enable right/left< via a digital input or Bus control. Does not depend
on the actual direction of rotation of the motor (e.g. following negated setpoint).
... 42 impulse functions:
Description below (only SK 500E … 535E).