SK 54xE – Users Manual for Frequency Inverters
128 BU 0505 EN-3021
HTL encoder function (only DIN2/4 )
For the evaluation of an HTL encoder, the digital inputs DIN2 and DIN4 must be parameterised with
the following functions.
Track A
HTL
encoder
This function
can only be
used for digital
inputs 2 (DIN2)
and 4 (DIN4)
!
A 24V HTL encoder can be connected to DIN 2 and DIN 4 in order to
measure the speed. The maximum frequency at the DIN is limited to
10kHz. Accordingly, a suitable encoder (low pulse number) or
suitable mounting (slow speed) SHOULD BE USED.
The direction of counting can be changed by exchanging the
functions on the digital inputs.
Further settings are in P461, P462, P463.
<10kHz
Track B
HTL
encoder
<10kHz
Pos: 261 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterüberschr ift - Fortsetzung Tabel le @ 1\mod_1331566123473_388. docx @ 18340 @ @ 1
Parameter
{factory setting}
Setting value / Description / Note Supervisor
Parameter
set
Pos: 262 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P400- P499/Parameter P426 – Sc hnellhaltezeit @ 0\mod_1328 000414237_388.doc x @ 10020 @ @ 1
P426
Quick stop time
(Quick stop time)
P
0 ... 320.00 sec
{ 0.10 }
Setting of the stop time for the fast stop function which can be triggered either via a digital input,
the bus control, the keyboard or automatically in case of a fault.
Emergency stop time is the time for the linear frequency decrease from the set maximum
frequency (P105) to 0Hz. If an actual setpoint <100% is being used, the emergency stop time is
reduced correspondingly.
Pos: 263 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P400- P499/Parameter P427 – Sc hnellhalt bei Störung [ SK 1x0E, SK 5xxE] @ 0\mod_1328000 585707_388.docx @ 10043 @ @ 1
P427
Emergency stop on error
(Emergency stop on error)
S
0 ... 3
{ 0 }
Activation of automatic emergency stop following error
0 = OFF: Automatic emergency stop following error is deactivated
1 = Mains supply failure: Automatic emergency stop following mains supply failure
2 = In case of faults: Automatic emergency stop following fault
3 = Fault or mains failure: Automatic emergency stop in case of fault or mains failure
An emergency stop can be triggered by the errorsE2.x, E7.0, E10.x, E12.8, E12.9 and E19.0.
Pos: 264 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P400- P499/Parameter P428 – Aut omatischer Anlauf @ 0\mod_132 8000652144_388.doc x @ 10066 @ @ 1
P428
Automatic starting
(Automatic starting)
S P
0 ... 1
{ 0 }
In the standard setting (P428 =0
Off
) the inverter requires a flank to enable (signal change
from "low high") at the relevant digital input.
In the setting On
1
the FI reacts to a High level. This function is only possible if the FI is
controlled using the digital inputs. (see P509=0/1)
In certain cases, the FI must start up directly when the mains are switched on. For this P428 = 1
On can be set. If the enable
signal is permanently switched on, or equipped with a cable
jumper, the FI starts up immediately.
NOTE: (P428) not "ON" if (P506) = 6, Danger! (See note on (P506))
Pos: 265 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P400-P499/Parameter P429 – Festfrequen z 1 @ 0\mod_1328000717565_38 8.docx @ 10089 @ @ 1