SK 54xEUsers Manual for Frequency Inverters
134 BU 0505 EN-3021
P480 [-01]
...
[-12]
Functional BusIO In Bits
(Bus I/O In Bits function)
S
0 ... 80
{ all 0 }
The Bus I/O In Bits are perceived as digital inputs (P420). They can be set to the same functions.
In order to use this function, one of the bus setpoints (P546) must be set to >Bus I/O In Bits 0-7
<. The required function must then be assigned to the relevant bit.
With the SK 54xE in association with IO extension modules (e.g. SK TU41OE) these I/O bits can
also process their input signals.
array SK 535E SK 54xE Comments
[-01] =
Bus / AS-i Dig In1
Bus / 2.IOE Dig In1
(Bus I/O In Bit 0)
[-02] =
Bus / AS-i Dig In2
Bus / 2.IOE Dig In2
(Bus I/O In Bit 1)
[-03] =
Bus / AS-i Dig In3
Bus / 2.IOE Dig In3
(Bus I/O In Bit 2)
[-04] =
Bus / AS-i Dig In4
Bus / 2.IOE Dig In4
(Bus I/O In Bit 3)
[-05] =
AS-i Initiator 1
Bus / 1.IOE Dig In1
(Bus I/O In Bit 4)
[-06] =
AS-i Initiator 2
Bus / 1.IOE Dig In2
(Bus I/O In Bit 5)
[-07] =
AS-i Initiator 3
Bus / 1.IOE Dig In3
(Bus I/O In Bit 6)
[-08] =
AS-i Initiator 4
Bus / 1.IOE Dig In4
(Bus I/O In Bit 7)
[-09] =
Flag 1
1)
[-10] =
Flag 2
1)
[-11] =
Bit 8 Bus control word
[-12] =
Bit 9 Bus control word
The possible functions for the Bus In Bits can be found in the table of functions for the digital
inputs. Function {14} "Remote control" is not possible.
1) The flag function is only possible with control via control terminals.
Pos: 298 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P400- P499/Parameter P481 Funktion Bu s I/O Out Bits [SK 5xxE] @ 0\mod_132800270309 5_388.docx @ 10802 @ @ 1
P481 [-01]
...
[-10]
Functional BusIO Out Bits
(Function of Bus I/O Out Bits)
S
0 ... 40
{ all 0 }
The bus I/O Out bits are perceived as digital outputs (P434).
They can be set to the same
functions.
In order to use this function, one of the bus actual values (P543) must be set to >Bus I/O In Bits
0-7 <. The required function must then be assigned to the relevant bit.
With the SK 54xE in association with IO extension modules (e.g. SK TU41OE) these I/O bits can
also process their input signals.
Array … SK 535E SK 54xE Comments
[-01] =
Bus / AS-i Dig Out1
Bus / AS-i Dig Out1
(Bus I/O Out Bit 0)
[-02] =
Bus / AS-i Dig Out2
Bus / AS-i Dig Out2
(Bus I/O Out Bit 1)
[-03] =
Bus / AS-i Dig Out3
Bus / AS-i Dig Out3
(Bus I/O Out Bit 2)
[-04] =
Bus / AS-i Dig Out4
Bus / AS-i Dig Out4
(Bus I/O Out Bit 3)
[-05] =
AS-i Actuator 1
Bus / 1.IOE Dig Out1
(Bus I/O Out Bit 4)
[-06] =
AS-i Actuator 2
Bus / 1.IOE Dig Out2
(Bus I/O Out Bit 5)
[-07] =
Flag 1
1)
Bus / 2.IOE Dig Out1
(Bus I/O Out Bit 6)
[-08] =
Flag 2
1)
Bus / 2.IOE Dig Out2
(Bus I/O Out Bit 7)
[-09] =
Bit 10 Bus status word
[-10] =
Bit 11 Bus status word
[-11] =
[-12] =
The possible functions for
the Bus Out Bits can be found in the table of functions for the digital
outputs or the relays.
For further details, please refer to the manual for the AS interface, BU 0090.
1) The flag function is only possible with control via control terminals.