5 Parameters
BU 0505 EN-3021 151
Pos: 364 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P500- P599/Parameter P550 Contro lBox Aufträge @ 0\mod_1328 098468764_388.doc x @ 12031 @ @ 1
P550
Back up data record
(Back up data record)
0 ... 3
{ 0 }
Within the optional ControlBox it is possible to save a data set (parameter set 1 … 4) of the
connected FI. This is saved in a non-
volatile memory within the Box, and can therefore be
transferred for other SK 5xxE units with the same database version (see P742).
0 = No change
1 = FI
ControlBox, the dataset is written from the connected FI to the ControlBox.
2 = ControlBox
FI, the dataset is written from the ControlBox to the connected FI.
3 = FI

ControlBox, the FI dataset is exchanged with the ControlBox dataset. With this
variant, no data is lost. It is continuously exchangeable.
NOTE:
If parameterisation from old FI's need to be loaded into FIs with new software (P707),
then the ControlBox must previous
ly be written to by the new FI (P550 = 1). The
dataset to be copied from the old FI can then be read out and copied to the new FI.
Pos: 365 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P500- P599/Parameter P551 Antr iebsprofi l (SK 5xxE) @ 0\mod_132809851713 9_388.docx @ 12054 @ @ 1
P551
Drive profile
(Drive profile)
S
0 … 1
{ 0 }
According to the option the relevant process data profiles can be activated with this parameter.
Note
Activation of profiles
This parameter is only effective for pluggable technology modules (SK TU3-…).
System
CANopen
DeviceNet
InterBus
Technology module SK TUx-CAO SK TUx-DEV SK TUx-IBS
Setting
0 = OFF =
USS protocol (Profile "Nord")
1 = ON =
DS402 profile AC Drives profile Drivecom profile