SK 54xE – Users Manual for Frequency Inverters
162 BU 0505 EN-3021
P746
Module status
(Module status)
S
0000 ... FFFF (hex) Shows the actual status (readiness, error, communication) of the technology unit (SK TU3-xxx),
but only when own processor is present, i.e. not for SK TU3-CTR.
Code details can be found in the respective BUS module manual. Different contents are shown
depending on the modules.
Pos: 429 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P700-P799/Parameter P747 – Umrichterspa nnungsbereich [S K 5xxE] @ 0\mod_1328178270094_388. docx @ 13520 @ @ 1
P747 Inverter Volt. Range
(Inverter voltage range)
0 ... 3
Indicates the mains voltage range for which this device is specified.
Pos: 430 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P700- P799/Parameter P748 – Statu s CANopen [SK 5xxE] @ 0\mod_1328178317375_38 8.docx @ 13543 @ @ 1
P748 [-01]
...
[-03]
Status CANopen
(CANopen status)
SK 520E or
higher
S
0000 ... FFFF (hex)
[01] = CANbus/CANopen status [-02] = reserved [-03] = reserved
Bit 0 = 24V bus voltage supply
Bit 1 = CANbus in "Bus Warning" status
Bit 2 = CANbus in "Bus Off" status
Bit 3 = System bus → Bus module online
(field bus module, e.g.: SK xU4-PBR)
Bit 4 = System bus → Additional module 1
online (I/O - module, e.g.: SK xU4-IOE)
Bit 5 = System bus → Additional module 2
online (I/O - module, e.g.: SK xU4-IOE)
Bit 6 = Protocol of the CAN module is 0 =
CAN or 1 = CANopen
Bit 7 = free
Bit 8 = "Bootsup Message" sent
Bit 9 = CANopen NMT State
Bit 10 = CANopen NMT State
Bit 11 ... 15 = free
CANopen NMT State Bit 10 Bit 9
Stopped =
Pre-Operational =
Operational =
0
0
1
0
1
0
Pos: 431 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P700- P799/Parameter P750 – S tatistik Ü berstrom @ 0\m od_1328178425687_38 8.docx @ 13566 @ @ 1
P750
Stat. overcurrent
(Overcurrent statistics)
S
0 ... 9999 Number of overcurrent messages during the operating period P714.
Pos: 432 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P700- P799/Parameter P751 – Sta tistik Überspannung @ 0\mod_1328178489671_388. docx @ 13589 @ @ 1
P751
Stat. Overvoltage
(Overvoltage statistics))
S
0 ... 9999 Number of overvoltage messages during the operating period P714.
Pos: 433 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P700- P799/Parameter P752 – Sta tistik Netzfehler @ 0\mod_1328178531108_388.d ocx @ 13612 @ @ 1
P752
Stat. mains failure
(Mains failure statistics)
S
0 ... 9999 Number of mains faults during the operating period P714.
Pos: 434 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P700- P799/Parameter P753 – Sta tistik Übertemperatur @ 0\mod_1328178578373_ 388.docx @ 13635 @ @ 1
P753
Stat. overtemperature
(Overheating statistics)
S
0 ... 9999 Number of overtemperature faults during the operating period P714.