SK 54xEUsers Manual for Frequency Inverters
172 BU 0505 EN-3021
Switch-on block messages
Display in the
SimpleBox /
ControlBox
Reason:
Text in the ParameterBox
Cause
Remedy
Group Details in
P700 [-03]
Pos: 483 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Infor mation I000_01 [SK 180E ... SK 5xxE] @ 2\mod_1347457775195_3 88.docx @ 47347 @ @ 1
I000
0.1 Disable voltage from IO
If the function "disable voltage"is parameterised, input (P420
/ P480) is at Low
Set "input High"
Check signal cable (broken cable)
0.2 IO fast stop
If the function "fast stop"is parameterised, input (P420 /
P480) is at Low
Set "input High"
Check signal cable (broken cable)
0.3 Block voltage from bus
For bus operation (P509): control word Bit 1 is
"Low"
0.4 Bus fast stop
For bus operation (P509): control word Bit 2 is
"Low"
0.5 Enable on start
Enable signal (control word, Dig I/O or Bus I/O) was already
applied during the initialisation phase (after mains "ON", or
control voltage "ON"). Or electrical phase is missing.
Only issue enable signal after completion of
initialisation (i.e. when the FI is ready)
Activation of "Automatic Start" (P428)
0.6 0.7 Reserved
Information message for PLC see supplementary
instructions
Pos: 484 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Infor mation I000_02-Ergänzung 0 8 und 09 [SK 180E ... SK 5xxE] @ 10\mod_14 55725649528_388. docx @ 306332 @ @ 1
0.8 Right direction blocked
Switch-on block with inverter shut-off activated by:
P540 or by "Enable right block" (P420 = 31, 73) or "Enable
left block" (P420 = 32, 74),
The frequency inverter switches to "Ready for switching on"
status
0.9 Left direction blocked
Pos: 485 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Infor mation I006 [SK 180E ... SK 5xxE] @ 2\mod_1347457929 759_388.docx @ 47372 @ @ 1
I006
6.0 Charging error
Charging relay not energised, because:
Mains / link voltage too low
Mains failure
Evacuation run activated ((P420) / (P480))
Pos: 486 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Infor mation I011 [SK 180E ... SK 5xxE] @ 2\mod_134 7457936856_388.doc x @ 47397 @ @ 1
I011
11.0 Analog Stop
If an analog input of the frequency inverter or a connected
IO extension is configured to detect cable breaks (2-10V
signal or 4-20mA signal), the frequency inverter switches to
the status "ready for switch-on" if the analog signal
undershoots the value 1 V or 2 mA
This also occurs if the relevant analog input is
parameterised to function "0" ("no function").
Check connections
Pos: 487 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Infor mation I014 "reserviert" [SK 200E ... SK 5xxE] @ 2\mod_1347457 944329_388.doc x @ 47422 @ @ 1
I014
14.4 Reserved
Error message for POSICON see supplementary
instructions
Pos: 488 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Infor mation I018 "reserviert" [SK 2xxE/ SK 5xxE] @ 2\mod_13 47457946544_388.d ocx @ 47447 @ @ 1
I018
18.0 Reserved
Information message for "Safe Stop" function see
supplementary instructions
Pos: 489 /Anleitungen/ Elektronik/F U und Starter/7. Technische Da ten/!Technische Dat en (Überschrif t) @ 0\mod_1328183045569_38 8.docx @ 13960 @ 1 @ 1