SK 54xE – Users Manual for Frequency Inverters
172 BU 0505 EN-3021
Switch-on block messages
Display in the
SimpleBox /
ControlBox
Reason:
Text in the ParameterBox
Cause
• Remedy
Group Details in
P700 [-03]
Pos: 483 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Infor mation I000_01 [SK 180E ... SK 5xxE] @ 2\mod_1347457775195_3 88.docx @ 47347 @ @ 1
I000
0.1 Disable voltage from IO
If the function "disable voltage"is parameterised, input (P420
/ P480) is at Low
• Set "input High"
•
Check signal cable (broken cable)
0.2 IO fast stop
If the function "fast stop"is parameterised, input (P420 /
P480) is at Low
• Set "input High"
• Check signal cable (broken cable)
0.3 Block voltage from bus
•
For bus operation (P509): control word Bit 1 is
"Low"
0.4 Bus fast stop
• For bus operation (P509): control word Bit 2 is
"Low"
0.5 Enable on start
Enable signal (control word, Dig I/O or Bus I/O) was already
applied during the initialisation phase (after mains "ON", or
control voltage "ON"). Or electrical phase is missing.
• Only issue enable signal after completion of
initialisation (i.e. when the FI is ready)
•
Activation of "Automatic Start" (P428)
0.6 – 0.7 Reserved
Information message for PLC see supplementary
instructions
Pos: 484 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Infor mation I000_02-Ergänzung 0 8 und 09 [SK 180E ... SK 5xxE] @ 10\mod_14 55725649528_388. docx @ 306332 @ @ 1
0.8 Right direction blocked
Switch-on block with inverter shut-off activated by:
P540 or by "Enable right block" (P420 = 31, 73) or "Enable
left block" (P420 = 32, 74),
The frequency inverter switches to "Ready for switching on"
status
0.9 Left direction blocked
Pos: 485 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Infor mation I006 [SK 180E ... SK 5xxE] @ 2\mod_1347457929 759_388.docx @ 47372 @ @ 1
I006
6.0 Charging error
Charging relay not energised, because:
•
Mains / link voltage too low
•
Mains failure
•
Evacuation run activated ((P420) / (P480))
Pos: 486 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Infor mation I011 [SK 180E ... SK 5xxE] @ 2\mod_134 7457936856_388.doc x @ 47397 @ @ 1
I011
11.0 Analog Stop
If an analog input of the frequency inverter or a connected
IO extension is configured to detect cable breaks (2-10V
signal or 4-20mA signal), the frequency inverter switches to
the status "ready for switch-on" if the analog signal
undershoots the value 1 V or 2 mA
This also occurs if the relevant analog input is
parameterised to function "0" ("no function").
• Check connections
Pos: 487 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Infor mation I014 "reserviert" [SK 200E ... SK 5xxE] @ 2\mod_1347457 944329_388.doc x @ 47422 @ @ 1
I014
14.4 Reserved
Error message for POSICON see supplementary
instructions
Pos: 488 /Anleitungen/ Elektronik/F U und Starter/6. Meldungen zu m Betriebszustand/Stör meldungen (Auflis tung)/Infor mation I018 "reserviert" [SK 2xxE/ SK 5xxE] @ 2\mod_13 47457946544_388.d ocx @ 47447 @ @ 1
I018
18.0 Reserved
Information message for "Safe Stop" function see
supplementary instructions
Pos: 489 /Anleitungen/ Elektronik/F U und Starter/7. Technische Da ten/!Technische Dat en (Überschrif t) @ 0\mod_1328183045569_38 8.docx @ 13960 @ 1 @ 1