EasyManua.ls Logo

Nordmann DC4 - Interrogation Of Unit Information

Nordmann DC4
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
34
Select the list with the unit information:
Path: Main menu > Diagnostic > Unit Status
Press <
> and < > keys, in order to select the unit information available in the list:
1 Steam capacity of the unit in kg/h
2 Total operating hours since the initial commissioning.
3 Actual status of the remote indication relay “Steam”
4 Actual status of the remote indication relay “Service”
5 Actual status of the remote indication relay “Error”
6 Actual status of the remote indication relay “Unit on”
7 Calculated mean drain time in seconds
8 Current average request
9 Actual status of the maximum level sensor
10 Counter showing the number of times the maximum level in the steam cylinder has been ex-
ceeded
11 Actual status of the inlet valve
12 Actual status of the drain pump
13 Actual status of the heating voltage relay
14 Current number of revolutions of the fan (appears only with units type RC4)
15 Current set address of the radio humidity sensor
16 Actual signal on address 1 of the radio humidity sensor
17 Actual signal on address 2 of the radio humidity sensor
18 Actual signal on address 3 of the radio humidity sensor
19 Actual signal on address 4 of the radio humidity sensor
Press the <Esc> key several times to quit the unit information list and to return to the standard op-
erating display.
4.7.2 Interrogation of unit information
Remote Error
O
Remote Unit On
O
Average Drain Time
0.0 s
Max. Level Sensor
Aus
Max. Level Counter
0
Inlet Valve
O
Outlet Pump
O
Main Contactor
O
Average Request
100%
Remote Service
Remote Steam
O 12.00.00
O 12.00.00
4
3
5
6
7
8
10
9
13
12
11
RF Hum. Addr
1
RF Hum. Status Addr 1
Init
RF Hum. Status Addr 2
Valid 46%rF
RF Hum. Status Addr 3
Bat. Low 46%rH
RF Hum. Status Addr 4
No Conn.
Fan Speed
0
14
15
16
17
18
19
Unit Status
4 kg/h
System Operation Hour
300h
System Capacity
11.11.2006 12.00.00
Esc Set
1
2
Menu
RC4 230V2
Standby
2011-10-31 12.00.00
Diagnostic
Unit Status :Set
Remote Test :Set
Modul Test :Set
ErrorHistory:Set
Esc Set
Main Menu
Engineering :Set
Diagnostic :Set
User :Set
Esc Set

Table of Contents

Other manuals for Nordmann DC4

Related product manuals