4.6.6 Activating/Deactivating fault current relay operation
Select “GFCI-Mode” in the settings menu, then press the <Set> key.
In the upcoming modication dialogue select whether or not the Nordmann RC4/DC4 is connected
to a fault current relay protected mains supply.
Factory setting: On
Options: On (mains supply with fault current relay protection)
Off (mains supply without fault current relay protection)
4.6.7 Water management settings
Select “Water Manag.” in the settings menu, then press the <Set> key.
The water management settings appear. Press the <
> and < > keys in order to select the individual
settings. Detailed information on the different settings are found in the following chapters.
4.6.7.1 Selecting the conductivity range of the supply water
Select “Conductivity” in the water management settings submenu, then press the <Set> key.
In the upcoming modication dialogue select the conductivity range of the supply water.
Factory setting: >125 μS/cm
Options: >125 μS/cm, <125 μS/cm
Settings
On/O Timer :Set
GFCI-Mode :On
Water Manag.:Set
Power Limit :Set
Date :31-10-11
Esc Set
GFCI-Mode
O
On
On
Esc Set
Water Manag.
Drain Factor:1.0
StandbyDrain:Full
StandbyDelay:72h
Conductivity:>125µS
Force Drain :On
Esc Set
Force Delay :72h
Water Manag.
Drain Factor:1.0
StandbyDrain:Full
StandbyDelay:72h
Conductivity:>125µS
Force Drain :On
Esc Set
Conductivity
>125µS
<125µS
>125µS
Esc Set
Settings
GFCI-Mode :On
Water Manag.:Set
Date :31-10-11
On/O Timer :Set
Time :12:00
Esc Set
Settings
GFCI-Mode :On
Water Manag.:Set
Date :31-10-11
On/O Timer :Set
Time :12:00
Esc Set