BACnet Protocol Implementation Conformance Statement (Normative) PIC Statement
45BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Standard Object Types Supported - Notification Class
Write Property/Add List element required for Intrinsic Reporting.
Data Link Layer Options
Device Address Binding:
Is static device binding supported? (This is currently necessary for two-way communication with
MS/TP slaves and certain other devices.)
• Select - Yes
•No
Networking Options:
• Select - Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-
MS/TP, etc. BACnet to Proprietary ARCnet Fire Network
• Annex H, BACnet Tunneling Router over IP
• BACnet/IP Broadcast Management Device (BBMD)
Does the BBMD support registrations by Foreign Devices?
•Yes
• Select - No
Character Sets Supported:
Indicating support for multiple character sets does not imply that they can all be supported
simultaneously.
If this product is a communication gateway, describe the types of non-BACnet equipment/
network(s) that the gateway supports:
Notifier Fire and Annunciator nodes compatible with NFN network v5.0 and later operating in a
network or stand-alone configuration.